Analisis dan Desain Filter Pasif Terhadap Harmonisa Pada Suatu Gedung Perkantoran = Fassive Filters for Harmonics in an Office Building

Usamah; Budi Sudiarto, supervisor; Faiz Husnayain, examiner; Fauzan Hanif Jufri, examiner; Ismi Rosyiana Fitri, examiner (Fakultas Teknik Universitas Indonesia, 2024)

 Abstrak

Penelitian ini dilakukan di suatu gedung perkantoran yang terletak di daerah Jakarta Selatan. Pada gedung ini banyak menggunakan beban non-linear yang memicu adanya harmonisa. Adanya gejala harmonisa ditandai dengan tingginya nilai THDI. Nilai THDI yang terukur dari transformator PUTR-1 sebesar 20,1% dan arusnya sebesar 1.525,80 A. Pada  penelitian ini bertujuan untuk mencari nilai derating factor akibat adanya gangguan harmonisa,  mendesain filter harmonisa (single passive tuned filter), menghitung seberapa besar pengaruh filter terhadap harmonisa dan menghitung seberapa besar investasi yang akan dikeluarkan jika filter diterapkan. Metode yang digunakan adalah memasukkan rumus-rumus kedalam aplikasi Microsoft Excel. Berdasarkan dari hasil perhitungan,  nilai dari derating factor tersebesar sebelum difilter yaitu sebesar 96,35% dari pembebanan maksimalnya. Untuk memimalisasi kerugian yang dihasilkan harmonisa, pada penelitian ini mencoba mendesain filter harmonisa (single passive tuned filter) dengan parameter-parameter C, L dan R pada orde harmonisa ke-3, 5, 11 dan 17 untuk desain 4 filter dan harmonisa ke-5 untuk 1 filter. Dari desain 4 filter dan 1 filter tersebut dapat menurunkan TDD ke-3 fasa, dapat menurunkan rugi-rugi daya. Selain itu penelitian ini juga memperkirakan seberapa besar investasi total dan memperkirakan seberapa lama payback periode berlangsung jika menerapkan 4 filter ataupun 1 filter.

This research was conducted in an office building located at South Jakarta. This building uses a lot of non-linear loads which trigger harmonics. The presence of harmonic symptoms is indicated by a high THDI value. The THDI value measured from the PUTR-1 transformer is 20.1% and the current is 1,525.80 A. In this study the aim is to find the derating factor value due to harmonic interference, design a harmonic filter (single passive tuned filter), calculate how big the influence is. filter for harmonics and calculate how much investment will be incurred if the filter is applied. The method used is to enter formulas into the Microsoft Excel application. Based on the calculation results, the value of the largest derating factor before filtering is 96.35% of the maximum load. To minimize losses resulting from harmonics, in this research we try to design a harmonic filter (single passive tuned filter) with parameters C, L and R in the 3rd, 5th, 11th and 17th harmonic orders for a design of 4 filters and 5th harmonics. for 1 filter. The design of 4 filters and 1 filter can reduce the TDD of all 3 phases, reducing power losses. Apart from that, this research also estimates total cost of investment and estimates how long the payback periode will last if 4 filters or 1 filter are applied.

 File Digital: 1

Shelf
 T-Usamah.pdf :: Unduh

LOGIN required

 Metadata

Jenis Koleksi : UI - Tesis Membership
No. Panggil : T-pdf
Entri utama-Nama orang :
Entri tambahan-Nama orang :
Entri tambahan-Nama badan :
Program Studi :
Subjek :
Penerbitan : Depok: Fakultas Teknik Universitas Indonesia, 2024
Bahasa : ind
Sumber Pengatalogan : LibUI ind rda
Tipe Konten : text
Tipe Media : computer
Tipe Carrier : online resource
Deskripsi Fisik : xiv, 74 pages : illustration + appendix
Naskah Ringkas :
Lembaga Pemilik : Universitas Indonesia
Lokasi : Perpustakaan UI
  • Ketersediaan
  • Ulasan
  • Sampul
No. Panggil No. Barkod Ketersediaan
T-pdf 15-24-13525496 TERSEDIA
Ulasan:
Tidak ada ulasan pada koleksi ini: 9999920544134
Cover